Digital ELCB Tester

Digital ELCB Tester

Digital ELCB Tester

Features

  • 2 Lines x 16 Characters L.C.D.
  • Very Low Consumption.
  • Microprocessor Controlled.
  • Menu Driven.
  • Accurate Digital readout of Disconnection Time.
  • Automatic data hold function.
  • Zero Crossing Circuitry permit testing at 0°or 180°.
  • EN 61010-1 CAT III 240V
  • Disconnection Phase Polarity Shown on L.C.D display.
  • Auto-Off and Off override.
  • Polarity Trip indicator (Positive or Negative Phase).
  • Wiring polarity indicator.
  • Measure voltage and friquency between Line and Earth before testing.
Current Settings 3mA, 5mA, 7mA, 10mA,15mA,
20mA, 30mA, 35mA,50mA,
100mA, 125mA,150mA, 175mA,
250mA,300mA, 375mA, 500mA.
Current Selection Rotary switch selector
Phase Start Selection  0°and 180° Referenced to Earth
Yes
Over-Temperature Protection Yes (3 sensors)
Wiring Correctness Indication Yes (LEDs)
Trip Indicator Yes (LCD)
Phase Polarity Trip Indicator Yes (LCD)
Referenced to Earth
Operating Voltage (L-E)
(50Hz or 60 Hz)
1812EL-A 240Vac
1812EL-B 230Vac
1812EL-C 220Vac
1812EL-D 110Vac
Voltmeter (L-E) 20Vac-280Vac
Timer Resolution 1mS (Max time=2.999S)
Timer Accuracy 1mS ±1mS
Current Accuracy ±5% ±1mA
Voltmeter Resolution 1Vac
Voltmeter Accuracy ±2%±1Vac
Operating Temperature - 5°C to 45°C
Storage Temperature - 10°C to 85°C
Power Source 8 x AA Batteries
Bat OK Led = Vbat > 7.5V
Measure battery voltage at
start up
Dimensions 170(L) x 165(W) x 92(D)mm
Weight Approx. 1020 g
(battery included)
Accessories Test leads
Shoulder belt
Instruction manual
Batteries